pix facebook
Enolgas Valvole Gas Valvole Gas di Sicurezza

Bon Tas

Gas ball valve with thermic safety device

The Bontas series is a range of valves equipped with a particular thermal safety device which intervenes in case of fire. As soon as the temperature of 100 ° is reached, the device blocks the escape of gas for a minimum of 60 minutes at a temperature of 925°.

The Bontas series ball valves meet the requirements contained in the EN 331 standard and are suitable for systems in accordance with the UNI EN 1775 standard.
The TAS thermal device can be supplied coupled with the ball valve or separately.

Refer to specific national/international standards, where existing, for countries others than Italy.

Material specification

Approved to EN 331

Enolgas Bon Tas caratteristiche

  

COMPONENT

MATERIAL

DESCRIPTION

 

1

BODY

CW 617 N UNI EN 12165

FORGED, NICKEL-PLATED

 

2

TAS DEVICE

MISCELLANEOUS

VARIOUS

 

3

BALL

CW 614 N UNI EN 12164

MACHINED, CHROME-PLATED

 

4

BALL GASKETS

P.T.F.E.

PURE

 

5

STEM

CW 614 N UNI EN 12164

MACHINED

 

6

THRUST WASHER

P.T.F.E.

PURE

 

7

O-RINGS

ELASTOMER

SUITABLE FOR USE WITH GAS EN549

 

8

LEVER HANDLE

ZINC-PLATED STEEL

PVC INSULATED

  

LEVER OR T-HANDLE

AL UNI5076

PAINTED

 

9

SELF-LOCKING NUT

8G STEEL

ZINC-PLATED

 


Characteristics

CHARACTERISTICS

The BON TAS valve is a combination of BON GAS ball valve and the TAS thermic safety device. Rapid on/off 90° turn operation. Gas flow capacity complies with UNI EN 331 standard.

STANDARDS

The BON TAS ball valve complies with UNI EN 331 and the thermic safety device complies with DIN VP 301.
BON TAS ball valve is suitable for installations in conformity with UNI EN 1775.

HOW THE DEVICE WORKS

The TAS thermic safety device works in the event of fire as soon as the temperature reaches 100°C, so blocking the fuel gas flow for at least 60 minutes at 925°C temperature.

END CONNECTIONS

For fuel gas 1^, 2^ e 3^ family 5 MOP.
For other uses from PN 80 (1/4”) to PN 16 (size 4”).
See pressure/temperature diagram.

WORKING PRESSURE

For fuel gas 5 MOP.

TEMPERATURE LIMITS

For fuel gas from -20°C to +60°C.

 

Enolgas Bon Tas caratteristiche

TAS Thermic safety device
The TAS thermic safety device works in the event of fire as soon as the temperature reaches 100°C.

Enolgas Bon Tas caratteristiche

Time/temperature diagram

  • Light up temperature of fuel gas: approx. 640°C
  • BON TAS strength point: 925°C

 

Download
Bon Tas 615.71 KB
  • G0255

    BON TAS TAS

    Thermic safety device for fuel gas, female/female.

    EAC
    DVGW
  • G0256

    BON TAS TAS

    Thermic safety device for fuel gas, male/female.

    EAC
    DVGW
  • G0261

    BON TAS

    Ball valve for fuel gas, female/female, with TAS thermic safety device, with lever handle.

    EAC
    Bureau Veritas
    DVGW
  • G0265

    BON TAS

    Ball valve for fuel gas, female/female, with TAS thermic safety device, with T-handle.

    EAC
    DVGW